Code Rule
680.12: Maintenance disconnecting means.
NEC Article Guide
Article 680 covers electrical installations for pools, spas, hot tubs, and fountains.
680.12: Maintenance disconnecting means.
680.21: Motors.
680.22: Receptacles.
680.23: Luminaires.
680.26: Equipotential bonding.
680.44: GFCI protection for spas.
According to NEC 2020, combination AFCI/GFCI devices are permitted to be used in which locations?
Correct Answer: Any location requiring both protections
Why: NEC 210.12(A)(6) allows combination AFCI/GFCI devices wherever both arc-fault and ground-fault protection are required
Under NEC 2020, what is the maximum interval allowed between GFCI testing?
Correct Answer: 30 days
Why: NEC 210.8 recommends testing GFCI devices monthly, which is 30 days maximum interval
Per NEC 2020 Article 250, equipment grounding conductor connections at GFCI devices must be made using:
Correct Answer: Listed connectors
Why: NEC 250.8 requires equipment grounding conductor connections to use listed connectors
According to NEC 2020, GFCI protection is required for temporary wiring installations exceeding:
Correct Answer: 90 days
Why: NEC 590.6(A) requires GFCI protection for temporary installations lasting more than 90 days
Under NEC 2020, which of the following areas requires AFCI protection for 120-volt branch circuits in dwelling units?
Correct Answer: Garages
Why: NEC 210.12(A) requires AFCI protection for garages in dwelling units
Drill category quizzes, study by NEC year, and sharpen your code recall with practical field-focused questions.