Code Rule
250.4: General requirements.
NEC Article Guide
Article 250 covers all grounding and bonding requirements.
250.4: General requirements.
250.24: Grounding service equipment.
250.28: Main bonding jumper.
250.52: Grounding electrodes.
250.53: Installation of electrodes.
250.64: GEC installation.
250.104: Bonding of piping.
250.118: EGC types.
250.119: EGC identification.
250.122: EGC sizing.
According to NEC 250.96, bonding of equipment grounding conductors must provide:
Correct Answer: Effective ground-fault current path
Why: NEC 250.96 requires bonding to provide an effective ground-fault current path for equipment grounding systems.
Per NEC 250.97, what bonding requirement applies to service raceways containing service conductors?
Correct Answer: Bonding required at both ends
Why: NEC 250.97 requires service raceways to be bonded at both ends to ensure electrical continuity.
According to NEC 517.19(F), isolated ground receptacles in health care facilities must be identified with what color?
Correct Answer: Orange face with orange triangle
Why: NEC 517.19(F) requires isolated ground receptacles in health care facilities to have an orange face with an orange triangle for identification.
Under NEC 250.32(B)(1), for separate buildings with one branch circuit, what grounding method is required?
Correct Answer: Equipment grounding conductor run with circuit conductors
Why: NEC 250.32(B)(1) requires an equipment grounding conductor to be run with the circuit conductors for separate buildings or structures.
According to NEC 250.4(A)(1), what is the primary purpose of grounding electrical systems?
Correct Answer: To limit voltage to ground during normal operation
Why: NEC 250.4(A)(1) states that grounding limits voltage to ground during normal operation and stabilizes voltage during ground faults.
Drill category quizzes, study by NEC year, and sharpen your code recall with practical field-focused questions.