Code Rule
240.4: Protection of conductors.
NEC Article Guide
Article 240 covers overcurrent protection for conductors and equipment including fuses, circuit breakers, and their ratings.
240.4: Protection of conductors.
240.6: Standard ampere ratings.
240.21: Location in circuit.
240.24: Location in premises.
240.87: Arc energy reduction.
According to NEC 230.24(B), what is the minimum clearance required for service drop conductors over residential driveways?
Correct Answer: 12 feet
Why: NEC 230.24(B) requires a minimum clearance of 12 feet over residential driveways and commercial areas not subject to truck traffic.
Per NEC 230.70(A), service disconnecting means must be located where in relation to the service entrance conductors?
Correct Answer: At the nearest point of entrance
Why: NEC 230.70(A) requires the service disconnecting means to be installed at a readily accessible location nearest to the point of entrance of the service conductors.
Under NEC 230.95, ground-fault protection of equipment is required for solidly grounded wye electrical services of more than how many amperes?
Correct Answer: 1000 amperes
Why: NEC 230.95 mandates ground-fault protection of equipment for solidly grounded wye electrical services of more than 1000 amperes.
According to NEC 230.85, what is required to be installed on service equipment?
Correct Answer: Surge protective device required
Why: NEC 230.85 requires surge protective devices to be installed on service equipment to protect against transient overvoltages.
Per NEC 230.42(A), the minimum size for service entrance conductors supplying loads consisting of not more than two 2-wire branch circuits is what AWG?
Correct Answer: 10 AWG
Why: NEC 230.42(A) requires a minimum of 10 AWG conductors for service entrance conductors supplying loads of not more than two 2-wire branch circuits.
Drill category quizzes, study by NEC year, and sharpen your code recall with practical field-focused questions.